Medium Voltage Variable Frequency Drive (MV VFD) 2015-07-30

Technical Specifications

 

Specification of DHVECTOL series medium voltage Variable Frequency Drive (VFD)

Model

DHVECTOL

Output power

250kVA ~ 25000kVA

Output voltage

3KV ~ 11KV

Control power supply

Single-phase AC220V, OR

3-phase AC380V 50Hz, OR

DC power supply 50Hz (optional).

Permissible input variation

Voltage: ±10%, frequency: ±5%

Control

Main circuit type

Medium Voltage Multi-level IGBT

Control mode

Speed sensor-less vector, V/F

Output frequency

0 ~ 50Hz/60Hz, accuracy: 0.01Hz

Speed up (down) time

1 ~ 3000s adjustable

Overload

125% for 60 seconds

Over current

150% of the rated output

Efficiency

>96% (with transformer)

Main control function

1.       Automatic restart upon instantaneous power failure

2.       Automatic power cell bypass and recovery

3.       Pre-charging

4.       Frequency hopping

5.       Flying start (optional).

Protective function

Overload, over current, cooling fan failure, main circuit abnormal etc.

Interfaces

Hardwired (optional: Profibus-DP, Modbus, Ethernet, GPRS)

Cabinet

Cabinet material

Steel plate

Ingress protection

IP20 (higher IP optional)

Vibration

Seismic zone

Cooling method

Air-blast

Cabinet color

RAL7032(other color optional)

Environment

Operating Temperature

0~+40, storage: -5~+50 (adjustable upon request)

Operating Humidity

≤90%

Elevation

≤1000m (adjustable upon request)

Installation

Indoor, in a dust free environment free of hazardous or flammable material.

Standards

GB, IEC, JIS

 

Key Features and Advantages

The high reliability of our VFD systems is achieved by multifold innovations including patented technologies of serial communication, pre-charging, automatic recovery, vertical ventilation & heat dispersion, and so on.

 

·         Patented communication technology

The communication between the control system and the power cells is in serial. Compared to parallel communication, the reliability of communication can be improved four times with this innovation.

 

·         Patented pre-charge technology

The pre-charging function can effectively control the charging speed of the capacitors, and thus charging shock can be prevented. Together with IGBT intelligent driving technology, the innovations can double the lifetime of the capacitors, from 5 years to 10 years for instance. The maintenance cost can be lowered significantly. 

 

·         Patented automatic recovery technology

With real-time monitoring, the VFD system can identify the causes of power cell bypass, and automatically restarts once it detects the problems are fixed. It ensures equipment to operate continuously and stably when the bus power supply has instantaneous failure.

·         Patented ventilation and heat dispersion method

Our VFD’s ventilation system is centralized and vertical. It has significant advantage over the distribution type in terms of temperature field control, air flow distribution, and wind speed uniformity. Since the capacitor units are located at the ventilation ducts, it is estimated that the lifetime of capacitor can be doubled, and thus the overall system service time is prolonged with this cooling mechanism.

 

Applications

VFD systems are used for speed controlling on fans, pumps, blowers, compressors, conveyors, feeders etc., for the industries of thermal power generation, mining, metallurgy, cement, petroleum & chemical, water supply & treatment, and so on.